Hit enter to search or ESC to close

Analogue input module CPX-E-4AI-U-I

CPX-E-4AI-U-I Part no.  4080493
  • Individual components for the automation system CPX-E
Select basic features

Pieces
Calculate delivery date
Close Technical Data
Show Technical Data
Dimensions W x L x H
18.9 mm x 76.6 mm x 124.3 mm
Vibration resistance
Transport application test with severity level 1 as per FN 942017-4 and EN 60068-2-6
Electrical connection input, function
Analog input
Note on ambient temperature
-5 - 60 °C for vertical installation
Intrinsic current consumption at nominal operating voltage for electronics/sensors
Typically 70 mA
Electrical connection for input, information on conductor cross section
0.2 - 2.5 mm² for flexible conductors without cable end sleeves
Diagnostics via bus
Lower limit value not complied with
Parameterization error
Parameter error
Upper limit value violated
Wire break
Sensor supply short circuit/overload
Overload at analog inputs
Underflow/overflow
Permissible voltage fluctuations for electronics/sensors
± 25 %
Electrical input connection, connection technology
Spring-loaded terminal
Shock resistance
Shock test with severity level 1 as per FN 942017-5 and EN 60068-2-27
Signal range
-20 - 20 mA
0 - 10 V
0 - 20 mA
1 - 5 V
-5 - 5 V
-10 - 10 V
4 - 20 mA
Electrical connection input, connection type
4x terminal strip
Module parameters
Analog input overload diagnostics
Response to analog input overload
Analog input data format
Sensor supply short circuit diagnostics
Deactivate sensor supply
Limit monitoring hysteresis
Response to short circuit/overload
Parameterization error diagnostics
Channel parameters
Wire break diagnostics
Upper limit diagnostics
Signal range per channel
Parameter error diagnostics
Underflow/overflow diagnostics
Smoothing factor
Lower diagnostic limit
Lower/upper limit
Diagnostics via LED
Faults per channel
Faults per module
Electrical connection input 2, function
Functional ground
Electrical connection input 2, connection type
Terminal strip
Electrical connection for input 2, information on conductor cross section
0.2 - 2.5 mm² for flexible conductors without cable end sleeves
Electrical input 2 connection, connection technology
Spring-loaded terminal
Electrical connection for input 2, connection pattern
00995842
Nominal operating voltage DC for electronics/sensors
24 V
Electrical connection, input, number of pins/wires
4
Electrical connection, input 2, number of pins/wires
4
Electrical connection for input, conductor cross section
0.2 mm² ... 1.5 mm²
Electrical connection for input 2, conductor cross section
0.2 mm² ... 1.5 mm²
Width dimension
18.9 mm
Type code
CPX-E
No. of inputs
4
Measured variable
Voltage
Current
Repetition accuracy
±0.1 % at 25 °C
Fuse protection (short circuit)
Internal electronic fuse per module
Operating error limit related to the ambient temperature range
+/- 0.3 %
Basic error limit at 25°C
+/- 0.2 %
Max. residual current of inputs per module
1.4 A
Power failure buffering
10 ms
Electrical isolation between channel and internal bus
yes
Electrical isolation between channels
no
CE marking (see declaration of conformity)
As per EU EMC directive
Corrosion resistance class (CRC)
0 - No corrosion stress
Storage temperature
-20 °C ... 70 °C
Relative air humidity
95 %
Non-condensing
Degree of protection
IP20
Ambient temperature
-5 °C ... 50 °C
Certification
RCM compliance mark
Product weight
96 g
Max. address capacity inputs
8 byte
Data format
15 bit + sign
Linear scaling
Max. cable length
Shielded
30 m
Type of mounting
With H-rail
Note on materials
Contains paint-wetting impairment substances
RoHS-compliant
Housing material
PA

Support / Downloads