Analogue module

CPX-2AA-U-I

526170

Product Documentation

Download Datasheet
Spare parts
Spare parts

Product Documentation

Download Datasheet
Pieces
Configurator is not supported on mobile devices
  • Accessories
  • Technical Data
  • Support / Downloads
Close Technical Data
Show Technical Data
Dimensions W x L x H
50 mm x 107 mm x 50 mm
(incl. interlinking block and connection system)
Type code
CPX
No. of outputs
2
Diagnostics
Parameterization error
Wire break per channel
Undervoltage of outputs
Limit value violation per channel
Actuator supply short circuit
Output signal short circuit per channel
Parameterization
Signal range per channel
Response to short circuit
Data format
Forcing per channel
Limit value monitoring per channel
Idle mode per channel
Measured value smoothing
Fail-safe modes per channel
Wire break monitoring per channel
LED indicators
1 group diagnostics
Internal cycle time
4 ms
Repetition accuracy
0.05 % at 25 °C
Fuse protection (short circuit)
Internal electronic fuse
DC operating voltage range
18 V ... 30 V
Intrinsic current consumption at nominal operating voltage
Typ. 100 mA
Operating error limit related to the ambient temperature range
±0.6 %
Basic error limit at 25°C
±0.5 %
Nominal operating voltage DC
24 V
Electrical isolation between channel and internal bus
Yes, without using the internal sensor supply
Electrical isolation between channels
no
Corrosion resistance class (CRC)
(when installed)
1 - Low corrosion stress
Storage temperature
-20 °C ... 70 °C
Degree of protection
Depends on manifold block
Ambient temperature
-5 °C ... 50 °C
Product weight
49 g
Data format
Scalable to 15 bits
12 bit + sign
Max. cable length
Shielded
30 m
Sensor type
0 - 10 V
4 - 20 mA
0 - 20 mA
Housing material
PC
PA-reinforced