Hit enter to search or ESC to close

Pressure sensor SPAE-P10R-Q3-PNLK-2.5K

Extremely small, extremely light, extremely convenient: The pressure transmitter SPAE monitors the pressure level of filtered compressed air from −1 to 0 and 0 to 10 bar. Ideal for vacuum monitoring for pick & place or for pressure monitoring in pneumatic applications.
SPAE-P10R-Q3-PNLK-2.5K Part no.  8001447
  • Electronic pressure sensor with piezoresistive pressure measuring cell, integrated signal processing, numeric pressure gauge in percent, operating key and a switching output, PNP/NPN switchable
  • Display of minimum and maximum readings
  • All parameters entered can be transferred to other SPAEs (replicator function)
  • Communication interface IO-Link®
Select basic features

Pieces
Calculate delivery date
Configure your product
Close Technical Data
Show Technical Data
Type code
SPAE
KC characters
KC EMC
Symbol
00995430
Certification
RCM compliance mark
c UL us - Recognized (OL)
CE marking (see declaration of conformity)
As per EU EMC directive
As per EU RoHS directive
Note on materials
RoHS-compliant
Measured variable
Relative pressure
Method of measurement
Piezoresistive pressure sensor with display
Pressure measuring range initial value
0 bar
Pressure measuring range end value
10 bar
Max. overload pressure
15 bar
Operating medium
Compressed air as per ISO 8573-1:2010 [7:4:4]
Information on operating and pilot media
Operation with oil lubrication possible
Temperature of medium
0 °C ... 50 °C
Ambient temperature
0 °C ... 50 °C
ADC resolution
10 bit
Accuracy in ± % FS
1.5 %FS
Repetition accuracy in ± %FS
0.3 %FS
Temperature co-efficient in ± %FS/K
0.05 %FS/K
Switching output
PNP/NPN switchable
Switching function
Freely programmable
Switching element function
Switchable
N/C contact
N/O contact
Max. output current
100 mA
Display range start value
0 %FS
Display range end value
99 %FS
Short-circuit protection
yes
Protocol
IO-Link®
IO-Link®, protocol version
Device V 1.1
IO-Link®, profile
Smart sensor profile
IO-Link®, function classes
Teach channel
Diagnostics
Binary data channel (BDC)
Identification
Process data variable (PDV)
IO-Link®, communication mode
COM2 (38,4 kBd)
IO-Link®, SIO mode support
Yes
IO-Link®, port class
A
IO-Link®, process data width OUT
0 Byte
IO-Link®, process data width IN
2 Byte
IO-Link®, process data content IN
14 bit PDV (pressure measurement)
2 bit BDC (pressure monitoring)
IO-Link®, minimum cycle time
3 ms
IO-Link®, data memory required
500 byte
DC operating voltage range
18 V ... 30 V
Reverse polarity protection
for all electrical connections
Electrical connection
Cable
Open end
3-wire
Cable length
2.5 m
Type of mounting
With accessories
Mounting position
Any
Pneumatic connection
QS-3
Product weight
40 g
Housing material
PA-reinforced
Sealing ring material
NBR
Display type
LED display
2-digit
Displayable unit(s)
%FS
Switching status indication
LED yellow
Setting options
IO-Link®
Via display and pushbuttons
Teach-in
Protection against tampering
PIN code
Threshold value setting range
1 % ... 98 %
Degree of protection
IP40
Corrosion resistance class (CRC)
2 - Moderate corrosion stress

Product Support