Output module

CPX-8DA-H

550204

Product Documentation

Technical data
Reliability datasheet
CAD data
Spare parts
CAD data
Spare parts

Product Documentation

Technical data
Reliability datasheet
Pieces

Loading...

Total (Please check cart for final price)

Configurator is not supported on mobile devices
  • Recommended Accessories
  • Technical Data
  • Support / Downloads
Close Technical Data
Show Technical Data
Dimensions W x L x H
(incl. interlinking block and connection system)
50 mm x 107 mm x 50 mm
No. of outputs
8
Diagnostics
Short circuit/overload per channel
Undervoltage of outputs
Parameterization
Fail-safe modes per channel
Forcing per channel
Idle mode per channel
Response to short circuit
Module monitoring
LED indicators
1 group diagnostics
8 channel diagnostics
8 channel status
Fuse protection (short circuit)
Internal electronic fuse per channel
Additional safety fuse
DC operating voltage range
18 V ... 30 V
Intrinsic current consumption at nominal operating voltage
Typ. 34 mA
Max. power supply per channel
2.1 A (50 W lamp load), per channel pair
Max. residual current of outputs per module
8.4 A
Nominal operating voltage DC
24 V
Electrical isolation between channel and internal bus
Yes, when using intermediate feed
Electrical isolation between channels
no
Corrosion resistance class (CRC)
1 - Low corrosion stress
(when installed)
Storage temperature
-20 °C ... 70 °C
Degree of protection
Depends on manifold block
Ambient temperature
-5 °C ... 50 °C
Product weight
48 g
Characteristic curve outputs
Based on IEC1131-T2
Switching logic at outputs
PNP (positive switching)
Housing material
PA-reinforced
PC