Proportional pressure control valve

VEAB-B-26-D2-F-A4-1R1

8046270

Product Documentation

Download Datasheet
Spare parts
Spare parts

Product Documentation

Download Datasheet
Pieces

Loading...

Total (Please check cart for final price)

Configurator is not supported on mobile devices
  • Recommended Accessories
  • Technical Data
  • Support / Downloads
Close Technical Data
Show Technical Data
Type code
VEAB
Valve function
3-way proportional pressure control valve
Type of control
Direct
Reset method
Mechanical spring
Actuation type
Electrical
Mounting position
Any
Sealing principle
Soft
Symbol
00995607
Ambient temperature
0 °C ... 50 °C
Temperature of medium
5 °C ... 50 °C
Storage temperature
-20 °C ... 70 °C
Dimensions W x L x H
18 mm x 67 mm x 66 mm
Pneumatic connection 1
Flange
Pneumatic connection 2
Flange
Pneumatic connection 3
Flange
Seals material
NBR
Type of mounting
Optionally:
With through-hole
With accessories
Inlet pressure 1 MPa
0 MPa ... 0.4 MPa
Inlet pressure 1
0 bar ... 4 bar
Inlet pressure 1 psi
0 psi ... 58 psi
Output pressure 2
0.001 MPa ... 0.2 MPa
Outlet pressure 2
0.01 bar ... 2 bar
Output pressure 2
0.145 psi ... 29 psi
Standard nominal flow rate
≥ 20 l/min
Standard nominal flow rate 2-3
≥ 20 l/min
Linearity error FS
0.5 %
Repetition accuracy in ± %FS
0.4 %FS
Hysteresis in ± %FS
0.25 %FS
Temperature coefficient
0.05 %/K
Absolute accuracy in ± %FS at room temperature
0.75 %FS
Product weight
70 g
Operating medium
Compressed air as per ISO 8573-1:2010 [7:4:4]
Inert gas
Information on operating and pilot media
Operation with oil lubrication not possible
Degree of protection
IP65
Certification
RCM compliance mark
KC characters
KC EMC
CE marking (see declaration of conformity)
As per EU EMC directive
Note on materials
RoHS-compliant
LABS conformity
VDMA24364 zone III
Corrosion resistance class (CRC)
2 - Moderate corrosion stress
DC operating voltage range
19 V ... 29 V
Nominal operating voltage DC
24 V
Residual ripple
10 %
Reference value
4 - 20 mA
Analog output signal range
4 - 20 mA
Precision analog output in ± %FS
2 %FS
Max. electrical power consumption
1 W
Reverse polarity protection
for all electrical connections
Short-circuit protection
For all electrical connections
Safety instructions
VEAA/VEAB safety position: if the electrical power supply is lost, the outlet pressure is maintained in uncontrolled form, it may increase or fall – pneumatic valve blocked.
Display type
LED
Electrical connection
4-pin
M8x1
Plug
as per EN 60947-5-2
Housing material